How to help the UK play heat network catch-up

Heat networks
Ensuring that we realise the best efficiency on heat networks, and provide great levels of service and thermal comfort for the occupants, requires due diligence, common sense and attention to detail both in the design and installation phases.

Charlie Mowbray, Senior Product Manager, Ideal Heating – Commercial, discusses the dos and don’ts of achieving an efficient, future proofed heat network.

Heat networks have never really taken hold in the UK in the same way that they have in other parts of Northern Europe, despite being a flexible, tried and tested technology used around the world for more than a century.

As other countries used the technology for safely and effectively heating buildings and generating instantaneous hot water around the world, the UK discovered gas in the North Sea and instead placed reliance on natural gas delivered direct to individual homes from the 1960s onwards.

Now that’s all set to change. As we’re all aware, the transformation of heat generation technology and products in the UK is necessary if we are to reach Net Zero in 2050, and no single type of technology will provide the solution.

Heat pumps are seen as one of the major technology types to realise our Net Zero ambitions, along with heat networks that are expected to provide up to 20% of heat in buildings by 2050. 

Benefits of a heat network

Heat networks will gladly take their heat input from different sources, making them both flexible and future proof, allowing for gas boilers now but able to readily swap to lower carbon alternatives, such as heat pumps, in the future. 

Heat networks are a highly scalable solution, regardless of the area covered by the network, or the number of buildings.  Furthermore, a single network can encompass dwellings and commercial buildings.

Unlike other types of heating, heat networks can be relatively easily retrofitted into existing properties where traditional heating appliances are being replaced.

Safety is another tick in the box for heat networks as there are no flue routes or gas connections to accommodate within a building, for either individual heating appliances or plant.

Components of a heat network

There are three core parts to a heat network: The energy centre (ie the central plant room), the distribution network, and the heat interface unit (HIU). The HIU is the appliance that transfers the thermal energy from the network to provide heating and hot water for the end user.

HIUs come in indirect or direct models. Indirect HIUs typically have two heat exchangers in the appliance and provide complete separation between the heat network for both heating and hot water. Direct HIUs usually have just the one heat exchanger that may separate heating or hot water from the network; at least one of the services they provide through a direct connection between the network and either the dwelling heating or hot water system. For example, Ideal Heating’s range of POD HIUs are available in both types, with domestic hot water outputs from 30 - 70kW, and feature highly-efficient stainless steel brazed plate heat exchangers.

HIU: some key considerations

Whilst the energy centre and distribution network represent the biggest capital costs of a heat network and are the most complex to get right, the heat cannot be transferred to each dwelling/building without the HIU. To ensure the network and the HIUs are operating in harmony, at their optimum, there are aspects that an installer should consider when choosing an HIU.

First and foremost, look for a Building Engineering Services Association (BESA) tested HIU. It enables you to see how that HIU performs under specific conditions and provides independently-certified levels of performance, rather than solely relying on manufacturers’ claims. 

Further to this, make sure that the performance of the HIU is confirmed for the current operating parameters of your particular network now and, just as importantly, for any future operating parameters.

I say ‘future’ because many heat networks may currently operate with gas boilers in the energy centre and a network temperature of 70°C or higher today, but that energy centre may be designed to accommodate conversion to a low or zero carbon energy course in the future such as an air source heat pump which typically operate most efficiently at lower temperatures. 

The HIU must be flexible enough to work efficiently at this lower network temperature; some cannot, which could be a costly and inconvenient mistake to rectify down the line. POD is designed to work across a broad range of primary temperatures, from 55°C upwards.

As well as BESA, the Chartered Institution of Building Services Engineers (CIBSE) has invested considerable time and expertise developing their code of practice. CIBSE CP1, Heat networks: Code of Practice for the UK, outlines examples of best practice or minimum standards that you should consider when making your selection.

Advice contained within CIBSE CP1 that I feel is particularly beneficial, and that often gets overlooked, includes design considerations for minimising the length of lateral runs in buildings from the main vertical risers; ensuring network pipe sizing is appropriate, not oversized which leads to increased heat losses and contributes to inefficient network operation; and ensuring that the selected HIU consistently delivers low return temperatures for the specific network operating conditions, across a range of loads.

Lastly, look at the manufacturer. What level of support do they provide, either at the front-end during design and specification of the network, or once the appliances are in service? Furthermore, always check the availability of the appliances and spares parts.

Mistakes to avoid

We see certain mistakes being repeatedly made in some aspects of heat networks and HIUs that you really should take great efforts to avoid.

Correct use of insulation is key to long term operating costs and efficiency of the network yet we keep seeing the thickness of insulation being reduced during value engineering or construction phases, probably to reduce costs. Even with the correct thickness, the standard of the installation of the insulation can have a dramatic effect on the efficiency of a network.

We’ve mentioned the importance of ensuring the HIU’s performance range when designing and specifying a system, including its ability to function at lower network temperatures to future proof the system. The same issues arise when it comes to the operator deciding to weather compensate the primary flow temperature from the energy centre in a bid to improve efficiency. 

This normally occurs in the summer months when the heating load is reduced. If the HIUs on that network aren’t designed or specified to operate with a reduced flow temperature, weather compensation can be counter-productive and the HIU may not be able to maintain the same duty for domestic hot water production, or it might cause an increased return temperature from the HIU. So, as before, take time to really consider your choice of HIUs and review the performance data.

Sticking with the temperature theme, it’s very important that you don’t leave a bypass open on the network, or on flushing valves before the HIUs, as this can vastly increase the return temperatures to the energy centre and have a detrimental effect on the network efficiency.

Commissioning of the HIU is where we can encounter a number of errors, all of which can lead to increased return temperatures to the energy centre. The main offender here is a failure to check that the required differential pressure is available at the HIU. 

Attention to detail

Heat Networks and Heat Interface Units are tried and tested technology, and a proven way in which we can help to decarbonise heat in buildings at scale. Ensuring that we realise the best efficiency on the networks, and provide great levels of service and thermal comfort for the occupants, requires due diligence, common sense and attention to detail both in the design and installation phases, and high quality appliances.

Related links:
Related articles:



modbs tv logo

First keynote speakers announced by Europump

The first two keynote speakers have been announced for an annual event being hosted by the British Pump Manufacturers Association (BPMA).

‘Landmark’ prosecution of online seller welcomed by REFCOM

The air conditioning and refrigeration industry’s largest safety register REFCOM has welcomed the successful prosecution of online sales company Appliances Direct (AD) for breaching F-Gas Regulations.